234 UDC 6300 Process Controller Product Manual 1/03
6.10 Input #5 - Pulse Inputs Calibration Procedure, Continued
Table 6-8 Input #5 Calibration Procedure, continued
Step Description Press Action
3
Calibrate Span
FUNC
L1/L2
You will see:
IN5 SPAN
Lower Display
(Value)
Upper Display
The value displayed represents 1/10 of the actual
calibration value.
For example: If 10,000 Hz is the desired span value,
enter 1000 for input 5 Span Value.
Minimum Span Value = 100 Hz (enter 10)
Maximum Span Value = 25,000 Hz (enter 2500)
or
to adjust the span value
4
Exit Calibration Mode
FUNC
L1/L2
then
LOWR
DISP
to store the calibration constants
to exit the calibration mode