1/03 UDC 6300 Process Controller Product Manual 111
4.11 Control Parameters Set Up Group
Introduction
The functions listed in this group deal with how the Single Loop Process
Controller or Loop 1 of a Two Loop Process controller will control the
process including: PV Source, Number of tuning parameter sets, Setpoint
source, Tracking, Power-up recall, Setpoint limits, Output direction, rate
and limits, Dropoff, Deadband and Hysteresis.
Control group
prompts
Table 4-10 lists all the function prompts in the Control setup group and
their definitions.
Table 4-10 Control Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
PV SOURCE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
IN ALG 1
IN ALG 2
PROCESS VARIABLE SOURCE - select the
source of the Process Variable.
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT ALGORITHM 1
INPUT ALGORITHM 2
PID SETS
NUMBER OF TUNING PARAMETER SETS — This
selection lets you choose one or two sets of tuning
constants (gain, rate, and reset).
1 ONLY
ONE SET ONLY — Only one set of tuning
parameters is available. Configure the values for:
Gain (proportional band),
Rate,
Reset Time, and
Cycle Time (if time proportional is used).
2KEYBD
TWO SETS KEYBOARD SELECTABLE — Two
sets of tuning parameters can be configured and can
be selected at the operator interface or by using the
Digital Inputs.
Press LOWR DISP
key until you see "PID SET1"
or “PID SET2” to switch between sets. Configure the
values for:
Gain, Rate , Reset, Cycle Time
Gain #2, Rate #2, Reset#2, Cycle#2 Time
See Subsection 5.10 for procedures.
2PV SW
TWO SETS PV AUTOMATIC SWITCHOVER —
When the process variable is GREATER than the
value set at prompt "SW VALUE" (Switchover
Value), the controller will use Gain, Rate, Reset, and
Cycle Time. The active PID SET can be read in the
lower display.
When the process variable is LESS than the value
set at prompt "SW VALUE," the controller will use
Gain #2, Rate #2, Reset #2, and Cycle #2 Time. The
active PID SET can be read in the lower display.
Other prompts affected: SW VALUE
Table 4-10 continued on next page