United Security Products AVD-45c Manual Página 196

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 195
182 UDC 6300 Process Controller Product Manual 1/03
5.13 Monitor 2 Loops of Control, Continued
Internal cascade
indication
When Internal Cascade has been configured, an “CAS” annunciator lights
as long as Loop 1 is operating in the remote setpoint mode (for example:
RSP is displayed).
If Local setpoint 1 and 2 is being used, the “CAS” will disappear until the
remote setpoint RSP CAS key is pushed to switch from local setpoint to
remote setpoint.
Switching between automatic and manual modes on either loop will not
affect the Internal Cascade indication.
Vista de página 195
1 2 ... 191 192 193 194 195 196 197 198 199 200 201 ... 301 302

Comentários a estes Manuais

Sem comentários