1/03 UDC 6300 Process Controller Product Manual 89
4.6 Algorithm Data Set Up Group, Continued
Table 4-5 Algorithm Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
IN ALG 1
(continued)
INPUT ALGORITHM 1 (continued)
FFWD MULT
FEEDFORWARD MULTIPLIER - applies to Loop 1
only and uses Input A, following a Ratio and Bias
calculation as a value multiplied by the PID
computed output value and sent, as an output value,
to the final control element. This algorithm will only
function in automatic mode.
Controller Output = PID Output x (Input A x Ratio + Bias )
AA
CONSTNT K
0.001 to 1000
WEIGHTED AVERAGE RATIO OR K CONSTANT
FOR MATH SELECTIONS - Only applicable for
algorithms "WTD AVG" or Math selections
"MUL DIV ", MULTIPLY ", "MULT DIV", or
"MULTIPLY"
CALC HIGH
–999 to 9999
CALCULATED VARIABLE HIGH SCALING
FACTOR FOR INPUT ALGORITHM 1 - Does not
apply to Feedforward Algorithms.
CALC LOW
–999 to 9999
CALCULATED VARIABLE LOW SCALING
FACTOR FOR INPUT ALGORITHM 1 - Does not
apply to Feedforward Algorithms.
ALG 1 IN A
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
OTHER ALG
OUTPUT 1
OUTPUT 2
ALGORITHM 1, INPUT A SELECTION - will
represent one of the available selections
OTHER ALG - Algorithm 1 is performed before
Algorithm 2. If ALG2 is used in ALG1, there is a
one cycle delay
ALG 1 IN B
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
OTHER ALG
OUTPUT 1
OUTPUT 2
ALGORITHM 1, INPUT B SELECTION - will
represent one of the available selections
OTHER ALG - Algorithm 1 is performed before
Algorithm 2. If ALG2 is used in ALG1, there is a
one cycle delay
ALG 1 IN C
NONE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
OTHER ALG
ALGORITHM 1, INPUT C SELECTION - will
represent one of the available selections
Table 4-5 continued on next page