1/03 UDC 6300 Process Controller Product Manual 117
4.12 Control2 Parameters Set Up Group, Continued
Table 4-11 Control2 Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
PID SETS
(CONTINUED
2SP SW
TWO SETS SP AUTOMATIC SWITCHOVER —
When the setpoint is GREATER than the value set at
prompt "SW VALUE" (Switchover Value), the
controller will use Gain3, Rate3, Reset3, and Cycle3.
When the setpoint is LESS than the value set at
prompt "SW VALUE," the controller will use Gain #4,
Rate #4, Reset #4, and Cycle #4.
Other prompts affected: SW VALUE
GAIN SCDL
GAIN SCHEDULING - allows you to schedule 8 user
defined Gain segments applied over a user defined
PV range. Enter Gain and PV values under Set Up
prompt "TUNING2".
ATTENTION
Gain scheduling automatically
disables Adaptive Tune for this loop.
PB or GAIN selections in "CONTROL" group also
applies.
SW VALUE
Value in engineering units
AUTOMATIC SWITCHOVER VALUE —This is the
value of Process Variable or Setpoint at which the
controller will switch from Tuning Constant Set #4 to
Set #3. Only appears when PID SETS selections
“2PV SW” or “2SP SW” are selected.
LSP's
LOCAL SETPOINT SOURCE — This selection
determines what your local setpoint source will be;
One local or Two local. Toggled by the SP1/SP2
key.
1ONLY
LOCAL SETPOINT — The setpoint entered from the
keyboard.
TWO
TWO LOCAL SETPOINTS — This selection lets you
switch between two local setpoints using the
SP1/SP2
key.
THREE
THREE LOCAL SETPOINTS — Setpoint 3 toggled
by RSP/CAS
key. LSP 3 is mutually exclusive
with RSP or Internal Cascade.
RSP SOURC
NONE
INPUT 2
INPUT 3
INPUT 4
INPUT 5
IN ALG 1
IN ALG 2
REMOTE SETPOINT SOURCE — this selection
determines what your remote setpoint source will be
when toggled by the RSP/CAS
key or Digital
Input.
NONE - No remote setpoint
INPUT 2 - Remote Setpoint is Input 2
INPUT 3 - Remote Setpoint is Input 3
INPUT 4 - Remote Setpoint is Input 4
INPUT 5 - Remote Setpoint is Input 5
IN ALG 1 - Remote Setpoint using Input 1 algorithm
IN ALG 2 - Remote Setpoint using Input 2 algorithm
Table 4-11 continued on next page