110 UDC 6300 Process Controller Product Manual 1/03
4.10 Input 5 Parameters Set Up Group, Continued
Table 4-9 Input 5 Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
BURNOUT5
NONE
UP
DOWN
BURNOUT PROTECTION (SENSOR BREAK) -
provides all input types with upscale or downscale
protection if the input fails.
NO BURNOUT - Failsafe output applied for failed
input but not out-of-range.
UPSCALE BURNOUT - will make the indicated PV
signal increase when a sensor fails, and flash in the
upper display. Do not use for Linear Input.
DOWNSCALE BURNOUT - will make the indicated
PV signal decrease when a sensor fails, and flash
the upper display. Do not use for Linear Input.
EMISSIV 5
0.01 to 1.00
EMISSIVITY FOR (RH) RADIAMATIC INPUTS - A
radiamatic pyrometer converts radiant energy
emitted by a target into electrical energy. Emissivity
is a correction factor applied to the radiamatic input
signal that is the ratio of the actual energy emitted
from the target to the energy which would be emitted
if the target were a perfect radiator.
Only available on Input 5 "RH" Radiamatic.