1/03 UDC 6300 Process Controller Product Manual 165
5.8 Setpoint Rate
Configuration
You can configure a Setpoint Ramp Rate that will apply to any Local
setpoint change immediately.
Refer to the Configuration Section to enable the ramp for either loop and
set an upscale or downscale rate value.
Make sure SP RAMP is disabled.
Operation
When a Local setpoint change is made, the controller will ramp from the
original setpoint to the new one at the rate specified. This changing
(current) setpoint can be viewed as SPn on the lower display.
Press the LOWR DISP key until you see SPn and the setpoint value in
the lower display.