United Security Products AVD-45c Manual Página 179

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 178
1/03 UDC 6300 Process Controller Product Manual 165
5.8 Setpoint Rate
Configuration
You can configure a Setpoint Ramp Rate that will apply to any Local
setpoint change immediately.
Refer to the Configuration Section to enable the ramp for either loop and
set an upscale or downscale rate value.
Make sure SP RAMP is disabled.
Operation
When a Local setpoint change is made, the controller will ramp from the
original setpoint to the new one at the rate specified. This changing
(current) setpoint can be viewed as SPn on the lower display.
Press the LOWR DISP key until you see SPn and the setpoint value in
the lower display.
Vista de página 178
1 2 ... 174 175 176 177 178 179 180 181 182 183 184 ... 301 302

Comentários a estes Manuais

Sem comentários